FULL LOAD CURRENT IN AMPERES, THREE PHASE CIRCUITS*
| 3 PHASE KVA= |
VOLTS x
AMPSx1.73
1000 |
| KVA |
208V |
240V |
480V |
| 3 |
8.3 |
7.2 |
3.6 |
| 4 |
12.5 |
10.8 |
5.4 |
| 6 |
16.6 |
14.4 |
7.2 |
| 9 |
25.0 |
21.6 |
10.8 |
| 15 |
41.0 |
36.0 |
18.0 |
| 22 |
62.0 |
54.0 |
27.0 |
| 30 |
83.0 |
72.0 |
36.0 |
| 45 |
124.0 |
108.0 |
54.0 |
| 75 |
208.0 |
180.0 |
90.0 |
| 112 |
312.0 |
270.0 |
135.0 |
| 150 |
416.0 |
360.0 |
189.0 |
| 225 |
624.0 |
541.0 |
270.0 |
| 300 |
832.0 |
721.0 |
360.0 |
*When motor service factor is greater than 1, increase full load amps proportionally. Example: If service factor is 1.15, increase above amp values by 15%.
|
|